MV Aerial Bundled Conductor (ABC) Cables

Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders to residential premises.

WhatsApp:

Share to

  • 产品描述
  • Application

    Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders to residential premises.

    Standard

    Basic design to IEC 60502 / AS/NZS 3599-1 standards

    Construction

    MV ABC
    Phase ConductorCircular compacted stranded H68 aluminium to BS2627.
    Conductor ScreenExtruded semi-conductive layer.
    InsulationXLPE.
    Insulation ScreenExtruded semi-conductive layer.
    metallic Screen(optional)Copper wire screen or copper tape screen.
    SeparatorSemi-conductive swellable tape.
    Outer SheathHDPE.
    Support ConductorGalvanized steel wires.
    AssemblyThree XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.

    Construction Parameters

    IEC 60502 6.35/11kV ABC for Overhead Distribution Lines

    Number of Cores x Nominal Cross Section

    No.×mm²

    Phase Conductor Stranding

    No.×mm

    Nominal Sectional Area

    mm²

    Maximum Conductor Resistance

    Ω/Km

    Messenger Suspension Unit Stranding

    No.×mm

    Nominal Sectional Area

    mm²

    Breaking Load

    KN

    Continuous current rating at 30°C ambient temp

    A

    3X50 + 1X2519/1.78500.6417/2.142560116
    3X70 + 1X5019/2.14700.4437/3.155062210
    3X95+ 1X5019/2.52950.327/3.05060173
    3X185+1X12037/2.521850.1647/4.67120150259
    3X150 +1X5037/2.251500.2067/3.155062365
    3X240 +1X5061/2.252400.1257/3.155062500

    Other cross-sections can be offered upon request.

    IEC 60502 19/33kV ABC for Overhead Distribution Lines

    Number of Cores x Nominal Cross Section

    No.×mm²

    Phase Conductor

    Stranding

    No.×mm

    Nominal Sectional Area

    mm²

    Maximum Conductor Resistance

    Ω/Km

    Messenger Suspension Unit

    Stranding

    No.×mm

    Nominal Sectional Area

    mm²

    Breaking Load

    KN

    Continuous current rating at 30°C ambient temp

    A

    3X50 + 1X2519/1.78500.6417/2.142560165
    3X150+ 1X5037/2.251500.2067/3.05060315
    3X185+1X7037/2.521850.1647/3.577091355
    3X70 +1X5019/2.14700.4437/3.155062250
    3X150 +1X5037/2.251500.2067/3.155062370

    Other cross-sections can be offered upon request.

    AS/NZS 3599 Part 1 6.35/11kV Al/XLPE /HDPE Non-Screened Cables

    Number of Cores x Nominal Cross Section

    No.×mm²

    Diameter of Conductor

    mm

    Thickness of Insulation

    mm

    Thickness of Insulation Screen

    mm

    Thickness of Sheath

    mm

    Messenger Suspension Unit

    Stranding

    No.×mm

    Nominal Sectional Area

    mm²

    Breaking Load

    KN

    3x356.93.40.81.27/4.7552.41370
    3x508.13.40.81.27/4.7554.61530
    3x709.73.40.81.27/4.7557.81790
    3x9511.43.40.81.27/4.7561.32100
    3x12012.83.40.81.219/3.5067.32540
    3x15014.23.40.81.219/3.5070.12840
    3x18515.73.40.81.219/3.5073.13190

    Other cross-sections can be offered upon request.

    AS/NZS 3599 Part 1 6.35/11kV AL/XLPE /CWS/HDPE Screened Cables

    Number of Cores x Nominal Cross Section

    No.×mm²

    Diameter of Conductor

    mm

    Thickness of Insulation

    mm

    Thickness of Insulation Screen

    mm

    Copper Wire Screen Stranding

    No.×mm

    Thickness of Sheath

    mm

    Galvanized Steel Wire Stranding

    No.×mm

    Nominal Sectional Area

    mm²

    Breaking Load

    KN

    Light Duty Screen
    3x356.93.40.825/0.851.87/2.0054.11820
    3x356.93.40.825/0.851.819/2.0058.12130
    3x508.13.40.825/0.851.819/2.0060.42300
    3x709.73.40.825/0.851.819/2.0063.62570
    3x9511.43.40.825/0.851.819/2.0067.02900
    3x12012.83.40.825/0.851.819/2.0069.83190
    3x15014.23.40.825/0.851.919/2.0073.03530
    3x18515.73.40.825/0.851.919/2.0076.03890
    Heavy Duty Screen
    3x356.93.40.840/0.851.87/2.0054.12050
    3x356.93.40.840/0.851.819/2.0058.12360
    3x508.13.40.823/1.351.819/2.0062.42820
    3x709.73.40.832/1.351.819/2.0065.63440
    3x9511.43.40.839/1.351.819/2.0069.04030
    3x12012.83.40.839/1.351.819/2.0071.84320
    3x15014.23.40.839/1.351.919/2.0075.04670
    3x18515.73.40.839/1.351.919/2.0078.05020

    Other cross-sections can be offered upon request.

    AS/NZS 3599 Part 1 12.7/22kV AL/XLPE /HDPE Non-Screened Cables

    Number of Cores x Nominal Cross Section

    No.×mm²

    Diameter of Conductor

    mm

    Thickness of Insulation

    mm

    Thickness of Insulation Screen

    mm

    Thickness of Sheath

    mm

    Messenger Suspension Unit

    Stranding

    No.×mm

    Nominal Sectional Area

    mm²

    Breaking Load

    KN

    3x356.95.50.81.27/4.7561.01780
    3x508.15.50.81.27/4.7563.31970
    3x709.75.50.81.27/4.7566.52260
    3x9511.45.50.81.27/4.7569.92600
    3x12012.85.50.81.219/3.5075.93070
    3x15014.25.50.81.219/3.5078.73390
    3x18515.75.50.81.219/3.5081.73760

    Other cross-sections can be offered upon request.

    AS/NZS 3599 Part 1 12.7/22kV AL/XLPE /CWS/HDPE Screened Cables

    Number of Cores x Nominal Cross Section

    No.×mm²

    Diameter of Conductor

    mm

    Thickness of Insulation

    mm

    Thickness of Insulation Screen

    mm

    Copper Wire Screen Stranding

    No.×mm

    Thickness of Sheath

    mm

    Galvanized Steel Wire Stranding

    No.×mm

    Nominal Sectional Area

    mm²

    Breaking Load

    KN

    Light Duty Screen
    3x356.95.50.825/0.851.87/2.0062.72280
    3x356.95.50.825/0.851.819/2.0066.72580
    3x508.15.50.825/0.851.819/2.0069.02780
    3x709.75.50.825/0.851.919/2.0072.63110
    3x9511.45.50.825/0.851.919/2.0076.03460
    3x12012.85.50.825/0.852.019/2.0079.23810
    3x15014.25.51.025/0.852.019/2.0082.84230
    3x18515.75.51.025/0.852.119/2.0086.24650
    Heavy Duty Screen
    3x356.95.50.840/0.851.87/2.0062.72510
    3x356.95.50.840/0.851.819/2.0066.72810
    3x508.15.50.823/1.351.819/2.0071.03300
    3x709.75.50.832/1.351.919/2.0074.63970
    3x9511.45.50.839/1.351.919/2.0078.04600
    3x12012.85.50.839/1.352.019/2.0081.24950
    3x15014.25.51.039/1.352.019/2.0084.85360
    3x18515.75.51.039/1.352.119/2.0088.25790

    Other cross-sections can be offered upon request.

    Technical Data

    Nominal Cross Section

    mm²

    Continuous Current Rating Still air

    A

    1m/s wind

    A

    2m/s wind

    A

    35105145165
    50125170200
    70150215250
    95180260300
    120205300350
    150230340395
    185265390450

● Contact us

Phone/Wechat

WhatsApp

Keywords:

Get More Product Information

*Note: Please fill in the information accurately and keep the communication open. We will contact you as soon as possible.

Submit

Related Products

Special mobile cables for various electric welding machines and equipment.
Go to Product View More
Special mobile cables for various electric welding machines and equipment.
Go to Product View More
Special mobile cables for various electric welding machines and equipment.
Go to Product View More
H05V-R cable is preferably for installation indoors, in cable ducts and in industrial plants or switching stations, under ground installation.
Go to Product View More
< 123 >